The timer shown in Figure 4.7 is reset on the first scan. On the second scan, it
starts timing. After 5seconds, it energizes a bit called“COMINIT”, which is used
to trigger the COM_REQ. It also energizes a bit called“RTMINIT”. On the next scan,
“COMINIT”is turned off, and the RTMINIT bit causes the timer to be disabled indefinitely.
Temporary (%T) data types are used for these two bits, so that their state is not
retained through a reset.After the COM_REQ has been executed, it writes status
data to the status register specified in theCOM_REQ data block. This register is
monitored by the ladder logic to determine the successful (or unsuccesful) result
of the COM_REQ. It is good practice to clear the status register just prior to execution
of the COM_REQ, ensuring the validity of future data.